Model: AW-CFP2166-2
Capacity: 2 Zone
Origin: China
INQUIRY
Why Choose Us?
- Satisfaction Guaranteed
- No Hassle For Return
- Cash on Delivery
Description
- The AW-CFP2166 series 2 Zone conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.
- 1.Maximum number of Analogue Conventional Detector Inputs: 20 detectors each zone
2.Available Options: 2-4 Zone and 6-8 Zone
3.outputs for Alarm devices: Includes 2 bells/fire relay/ fault relay
4.Auxiliary resettable power output: 24VDC/ 100mA limiting protection
5.Automatic power switchover: mains power and secondary power (from batteries)
6.Independent functional buttons with indication: User friendly interface for easy operation and recognition
7.Access levels to enter the panel
8.Fault supervision and notification: inputs, outputs, system, power, earth, fuse
9.Disablement: zones disablement 10.Evacuation: Fire drills to simulate fire alarm condition on panel
11.Silence: sounders and buzzer silence 12.Walk test: indicators check -
AC INPUT 220VAC 50/60Hz +10% -15% DC OUTPUT 24VDC typical Voltage for MCU 5V for MCU Current at 24VDC from PSE 450mA standby current Maximum current from PSE 1A except batteries charge Batteries current 1.85A maximum, current limited Auxiliary output 24VDC +/- 10%, 100 mA max,
current limited, monitoredBatteries 2*12V/ 2.3Ah sealed lead acid gel,
self-regulated *Battery low-voltage protection 21V Detectors connection allowed each zone 20 (except MCPs) Zone alarm current 6mA minimum/ 27mA maximum Sounder output 2*0.75A maximum Fire Relay 1A/30VDC maximum Fault Relay 1A/30VDC maximum Communication protocol 2 wires RS485 bus system EOL resistor for zone 6.8K 1W EOL resistor for outputs 6.8K 1W Fuse for AC Power 1 A/ 250V glass tube fuse 5 X 20mm Fuse on DC Power 1A/ 250V glass tube fuse 5 X 20mm Environmental Class A temperature range: -5 to 50°C
Humidity: 5 to 95% RH, non-condensingTerminal blocks rating All terminals rated for 12 to18 AWG
(0.75 to 2.5 mm2)