Vane type waterflow detector (Vane type waterflow switch)
- Certificate: UL Listed / FM Approved
- Standard: UL 346, comply to NFPA 13, 13D, 13R, 72
- Trigger threshold: Flow rate 4 ~ 10 GPM
- Max surge: 18 FPS (Feet per second)
- Retard time: 0-90 second delay, field replaceable
- Temperature: 0°C to 49°C
- Pressure rating: 250 / 450 / 300 psi
- Surface: FBE coating as AWWA C550
INQUIRY
![]()
Why Choose Us?
- Satisfaction Guaranteed
- No Hassle For Return
- Cash on Delivery
Description
Vane type waterflow detector (Vane type waterflow switch) installed in wet sprinkler system provides an electrical alarm. When water movement deflects the vane inserted in waterway, and the motion is transmitted to an alarm-actuating switch after a predetermined time delay.
Available size
| Compatible steel pipe | Connection | Working pressure (psi) | Ref. No. |
|---|---|---|---|
| Pipe 1″ ~ 2″ / DN25 ~ 50 | Threaded, NPT | 250 / 450 | V8501 (UL/FM)* |
| Pipe 2″ / DN50 | U-bolt | 450 | V8502 (UL/FM) |
| Pipe 2-1/2″ / DN65 | U-bolt | 450 | V8503 (UL/FM) |
| Pipe 3″ / DN80 | U-bolt | 450 | V8504 (UL/FM) |
| Pipe 4″ / DN100 | U-bolt | 450 | V8505 (UL/FM) |
| Pipe 5″ / DN125 | U-bolt | 450 | V8506 (UL/FM) |
| Pipe 6″ / DN150 | U-bolt | 450 | V8507 (UL/FM) |
| Pipe 8″ / DN200 | U-bolt | 450 | V8508 (UL/FM) |
| Pipe 10″ / DN250 | U-bolt | 300 | V8509 (UL) |
Note: *For threaded type, 12 different paddles are furnished. The threaded waterflow detector fits pipe size 1″, 1-1/4″, 1-1/2″ and 2″ through its 1″ NPT end threading into a tee (Tee size includes 1″ x 1″ x 1″, 1-1/4″ x 1-1/4″ x 1″, 1-1/2″ x 1-1/2″ x 1″, 2″ x 2″ x 1″). When installation, the installer shall select the proper paddle for the pipe size and tee type, so to ensure the proper installation depth and clearance of the waterflow detector to the tee.